STANDARD CONTROL PANEL FOR 75-437 KVA DG SET

Bill Of Material For Our Standard Panel

(Rating of switchgears are suitable for Panel KVA Rating. Additional Components can also be provided depending upon Customers requirement)

Item 75-110 KVA 125-140 KVA 160-180 KVA 200-250 KVA 320-437 KVA
Ammeter ,96 sq. mm Make - AE/IMP 150/5, C.T. TYPE 200/5, C.T TYPE 300/5,  C.T TYPE 400/5,C.T. TYPE 600/5, C.T. TYPE
Voltmeter, 96 sq. mm Make - AE/IMP 0-500V 0-500V 0-500V 0-500V 0-500V
Frequency Meter, 96 sq. mm Make - AE/IMP 45-55HZ 45-55HZ 45-55HZ 45-55HZ 45-55HZ
KW Meter, 96 sq.mm Make - AE/IMP X X 300/5 400/5 600/5
Hour Meter, make - Kaycee X 41/2 digit 230Vac 41/2 digit  230Vac 41/2 digit 230Vac 41/2 digit 230Vac
Voltmeter Sel. Switch Rotary type 10A Make -Kaycee/Salzer R-Y-B-OFF R-Y-B-OFF R-Y-B-OFF R-Y-B-OFF R-Y-B-OFF
MCCB with Shunt trip Make-Havells (3-pole) 125/150A 200A 250A 300A/400A 630A
Current Tranformer Tape Wound Type               make - MDC/Kappa 150/5

3 Nos.

200/5

3 Nos.

300/5

3 Nos

400/5

3 Nos

600/5

3 Nos.

Control Fuse  HRC type    Make- S&S/FTC, 6A, 4 nos. 6A, 4 nos. 6A, 4 nos. 6A, 4 nos. 6A, 4 nos.
Indicating Light (L.E.D. Type)   make-FTC 3 nos. 3 nos. 3 nos. 3 nos. 3 nos.

 

Dimensions of Standard Control panel in mm

Panel Type

Height  (H) Width (W) Depth (D) Meter Height Cable Connection Clearance
75-140 KVA 1400 560 370 1280 150
160-380 KVA 1700 600 460 1580 350
437.5 KVA 1900 900 600 1750 450

 

 

Wiring Diagram for 75-140 KVA DG Standard Panel

dwg50.gif (10189 bytes)


 

Wiring Diagram for 160-437 KVA DG Standard Panel

dwg75-437.gif (10418 bytes)


Home | Introduction | Standard Panel |Site Info. | Trouble Shooting | Quality Policy | Contact Info